SU-RN standard mine control station
Station circuitry provides:
-
Power contactors engagement/disengagement by a preset algorithm
-
Power contactors engagement/disengagement with de-energized power circuit (testing)
-
Compatibility with remote controls
-
Intrinsically safe inputs for external control circuits
-
Intrinsically safe outputs for power contactor status signals
-
Short-circuit current protection of power branches
-
Overcurrent protection of power branches
-
Overheating protection of downstream equipment
-
Remote control circuit fault or short-circuit protection
-
Prevention of self-engagement at 150% of rated voltage
-
Protection against branch ground circuit failure or resistance buildup over the allowable value
-
Branch interlock in case of external line-to-ground insulation fault or drop below the allowable level
-
Current leakage protection in internal 220V power lines
-
No-voltage protection
-
Mains power indication
-
Tripping event indication
-
Branch line engagement indication
-
Protection testing
Main station types according to downstream equipment:
Compact station with an automatic circuit breaker and a lighting transformer to control a shearer, a face machine, and a cooling plant
Compact station with an automatic circuit breaker to control a shearer and a cooling plant
Compact station with a transformer (P=40kVA, U=1140/660V) to control face conveyors and gate conveyors
Compact station to control face conveyors and gate conveyors
Compact station to control stowage complexes
Environment conditions:
-
Climatic version: U5 (temperate)
-
Ambient temperature: minus 5°C to +35°C
-
Relative humidity: (98±2)% at (25±2)°C
-
Atmospheric pressure: (99.75±13.3) kPa
-
Dust concentration in air: max. 1200 mg/m3
-
Vibration: max. 25 Hz
-
Vibration acceleration: max. 10 m/s2
-
Mechanical impact exposure group: M6
-
Severe shock or impact: not allowed
-
Working position: vertical, with deflection by max. 15° in any direction
-
Allowable power mains voltage fluctuations: 85% to 110% of rated value
Main performance specifications
Property |
Value |
---|---|
Rated feed voltage, V |
1140/1000/660 |
AC mains frequency, Hz |
50 |
Rated trip current, A |
1250 |
Branch line insulation control unit adjustment range, kΩ |
10...130 |
Branch line current leakage control unit adjustment range, kΩ |
10...130 |
Power circuit current leakage trip time adjustment range, s |
0.1...0.5 |
Ex rating |
RN2 - [Ех iа] I |
Enclosure protection rating, min. |
IР54 |
Remote control circuit intrinsic safety rating |
iа |
Duty modes: continuous short-time intermittent |
S1 |
Weight. kg |
3500 |