SU-RN PCh standard mine control station with frequency converter
Provide protections and interlocks for 3-phase AC driving motors, subject to frequent acceleration, deceleration, or inversion of rotation direction, in particular, like:
-
belt or drag link conveyor drives,
-
pump drives,
-
fan drives,
-
electric vehicle drives, etc.
The stations are designed to work at 660V to 1140V, including at underground mines and shafts with gas and/or combustible dust hazard. A station can be either non-Ex (standard) or Ex version.
Station protections:
-
Overcurrent and short-circuit current protection for every branch line (setting according to the motor rated current)
-
Engine feeding interlock in case of branch line insulation drop below the threshold value (30kΩ or 100kΩ)
-
Drive motor overheating protection
-
Ground circuit fault or resistance rise protection (if the station and motor are installed at a moving unit)
Characteristic features:
The main special feature of the station is the frequency converter air cooling within the entire available power range, while water cooling is most commonly used at explosion-proof frequency converters nowadays which is much costlier and invokes certain operating issues (the need to service pumps, to clean filters and water pipelines, to monitor and control cooling circuit pressure; leakage risk) that are not applicable to air cooling. The air cooling system is maintenance-free within the entire service life.
Scope of application and main advantages:
-
Belt conveyor drives
-
Drug link conveyor drives
Main performance specifications
Property |
Value |
||
---|---|---|---|
Version |
660V |
1140V |
|
Feeding |
Voltage |
560 ~760 V |
970 ~ 1310 V |
Frequency |
47-63 Hz |
47-63 Hz |
|
Rated power |
55 — 500 kW |
110 — 630 kW |
|
Rated output current |
63 — 540 А |
73 — 400 А |
|
Cooling |
Air-cooled |
Air-cooled |
|
Duty mode |
|
2-quadrant |
4-quadrant |
|
Control mode |
Vector control (VC), vector control with no speed sensor (SVC), U/f mode |
|
U/f mode |
Linear, multipoint type, voltage-frequency curve |
||
Control source |
Panel, binary inputs/outputs, network |
||
Rate setting source |
Digital signal, analogue signal, repetitive frequency signal, network signal, PLC signal, PID controller signal, etc. All modes can be combined or switched over |
||
Power balance |
Master/slave communication |
||
Overload resistance |
150% of rated current: 60 s 180% of rated current: 10 s |
||
Speed range |
1:100 (SVC), 1:1000 (VC) |
||
Speed monitoring accuracy |
±0.5% of max. speed (SVC), ±0.1% of max. speed (VC) Digital setting: 0.01 Hz |
||
Frequency resolution |
Analogue setting: 0.1%* |
||
Control properties |
Acceleration/ deceleration mode |
Linear or S-curve, 4 acceleration/deceleration time groups |
|
Jogging mode |
Jogging frequency: 0.0 Hz to max. output frequency Jogging acceleration/deceleration time: 0-3600.0 s |
||
Integral process PID controller function |
Available closed-loop control system |
||
Automatic intermediate loop voltage controller |
To maintain steady intermediate loop voltage with mains voltage fluctuations |
||
Torque setting source |
Control panel, input analogue signal, network |
||
Protection functions |
Over 30 functions to protect against, for example, overcurrent, overvoltage, power voltage fault, overheating, phase fault, short-circuit, overload, etc. |
||
Control interface |
Colour with error and alarm recording, monochromic, remote control |
||
Communication |
Communication protocol |
PROFIBUS, MODBUS, CAN, Ethernet |
|
Ex rating |
РВ Ex d[ia] I — SU-RV PCh |
||
Enclosure protection rating |
IP 54 |
||
Ambient conditions |
Temperature |
-10о ~ +50оС |
|
Altitude above sea level |
Max. 1000 m with no prejudice to performance |
||
Humidity |
5%~95% non-condensing |